Viking VSF300 Intelligent Video Flame Detector

The Viking VSF300 is an explosion-proof intelligent video flame detector (iVFD) capable of detecting an n-heptane (gasoline) fire at 200 feet and JP4 (kerosene-gasoline blend jet fuel) at 300 feet. The detector processes live video images to detect the characteristic properties of flames using onboard digital signal processing (DSP) and advanced software algorithms.

Features

• Comprehensive design support and services provided by Viking Integrated Safety
• Intelligent visual flame detection (iVFD) principle ensures maximum false alarm immunity and eliminates sensitivity loss in the presence of modulated sunlight and black body heat
• Continuous optical test, without a reflector
• Verifies operation and improves device up-time
• Microprocessor controlled heated-optics
• Maintains operation in harsh weather conditions (snow, ice, condensation)
• International hazardous area approvals: FM / ATEX / IEC Ex
• Certified performance testing to multiple fuels: FM 3260 / EN 54-10
• Spatially aware—single sensitivity detection
• External testing with a long-range flame simulator minimizes the need for scaffolding
• Easy integration using industry-standard outputs: Alarm and Fault Relays, 0–20mA, HART as standard
• Certified SIL 2 capable
• Worldwide marine approvals

Viking Part Numbers

Viking Part = Viking Model :: Suffix :: Housing :: Cable Entry

24372 = VSF300 IVFD :: -NPT :: Aluminum :: ¾” NPT
24373 = VSF300 IVFD :: -M25 :: Aluminum :: M25
24374 = VSF300 IVFD :: -NPT-SST :: Stainless Steel :: ¾” NPT
24375 = VSF300 IVFD :: -M25-SST :: Stainless Steel :: M25

Certifications

FM Approved
Class 1 Div 1, Groups B, C, D T4
Class 1 Zone 1 AEx/Ex db IIC T4
Ambient –50°C to +85°C

ATEX Ex II 2 G Ex db IIC T4
IECEx Ex db IIC T4
Ambient –60°C to +85°C

INMETRO Ex db IIC T4
PESO Ex db IIC T4
Ta= –60°C to +85°C

Performance approvals:
FM 3260
EN 54-10

Ingress:
IP66 / NEMA type 4X

IEC 61508:
Certified SIL 2 Capable

Marine:
DNV GL Type Approval
ABS Product Assessment

Operating Specs

Parameter: Min—Max

Range (Depth of Field): 2m—60m
Horizontal Field of View: 120°
Vertical Field of View: 80°
Detector Response Time: 4.2s—30s
Power-on Reset Delay: 5s
Optical Verification: OFF by default

Technical Data & Applications Brochures (EN = English, DE = German)