ServersCheck Fuel Leak Detection Sensor

Low-cost sensor for monitoring fuel leaks 24x7 from fuel tanks for generators or fuel pipes. The fuel leak sensing cable may be used in Class I, Division 2, Groups A, B, C, D Hazardous Locations. If wiring from the module meets requirements for intrinsic safety, sensing cable may be used in Class I, Division 1, Groups A, B, C, D Hazardous Locations (Zone 0 or Zone 1 in Europe). The default cable length is 14ft / 4.5m and can be extended to 100ft / 30 m. The fuel leak sensing cable is designed for single use only. The IP, Modbus TCP, Modbus RTU (RS-485) & SNMP based fuel leak cable can detected following fuel types:
Fuel type | Typical response time at 20°C (68°F) |
#1 diesel fuel | 60 minutes |
#2 diesel fuel | 120 minutes |
Gasoline | 12 minutes |
JP5 jet fuel | 70 minutes |
JP8 jet fuel | 50 minutes |
Jet-A jet fuel | 50 minutes |
Viking Part Number: ENV-FLEAK-COMBO
Features
— plugs into the base unit
— powered by the base unit
— Leak Detecting Sensing cable is made in the USA
— alerts via SNMP Traps, email, SMS or voice calls
— expandable up to 100m/330ft per sensor
— sensing cables are approved for installation in ordinary and hazardous areas
— sensing cables are mechanically strong and resistant to corrosion and abrasion
— single use sensing cable
— triggers an alert when fuel touches the cable
— detect fuel types: #1 diesel fuel , #2 diesel fuel, Gasoline, JP5 jet fuel, JP8 jet fuel and Jet-A jet fuel